VulnTideExploited vulnerabilities, by vendor. Data as of .
Not in CISA KEVReported exploited: VulnCheck KEV since Published CVSS 9.8 criticalEPSS 5.5% probability of exploitation in 30 days
Rockwell Automation

CVE-2023-3595: Rockwell Automation ControlLogix Communication Modules Vulnerable to Remote Code Execution

Is it exploited?

Reported, not confirmed by CISA. VulnCheck KEV lists it as exploited in the wild. CISA has not added it to its Known Exploited Vulnerabilities catalog as of .

VulnCheck KEV lists it since . It cites 1 public report, the first from .

How likely is exploitation in the next 30 days?
5.5%

EPSS score, percentile 92.8 of all scored records. A probability estimated by FIRST, not a report of exploitation.

How severe?
9.8 Critical

CVSS v3.1 base score, given by the CNA

What should I do?

* Update firmware. Full textSolution from the CVE record.

CISA has set no required action, because the vulnerability is not in KEV.

The CVE record links no vendor advisory, patch or mitigation.

Which versions are affected?

Affected

  • <=5.008 & 5.028
  • <=11.003
  • <=5.008 & 5.028
  • <=5.008 & 5.028
  • <=11.003
  • <=11.003

and 14 more in the table below

Versions by product

Source: CISA KEV 2026.10.29, as of ; VulnCheck KEV, as of ; FIRST EPSS, as of ; CVE List, as of . About the data.

Description

Rockwell Automation ControlLogix Communication Modules Vulnerable to Remote Code Execution

Where this vulnerability exists in the Rockwell Automation 1756 EN2* and 1756 EN3* ControlLogix communication products, it could allow a malicious user to perform remote code execution with persistence on the target system through maliciously crafted CIP messages. This includes the ability to modify, deny, and exfiltrate data passing through the device.

Source: CVE List, as of . About the data.

What to do

Advisories and patches

The CVE record links no vendor advisory, patch or mitigation.

Solution (from the CVE record)

* Update firmware. Update EN2* ControlLogix communications modules to mitigated firmware. * Properly segment networks. Given a cyber actor would require network connectivity to the communication module to exploit the vulnerability, organizations should ensure ICS/SCADA networks are properly segmented within the process structure as well as from the Internet and other non-essential networks. * Implement detection signatures. Use appended Snort signatures to monitor and detect anomalous Common Industrial Protocol (CIP) packets to Rockwell Automation devices.

This summary is based on the CVE record as of . Check the vendor's advisory before you act: affected versions and fixes can change.

Affected products and versions

Versions by product, as listed in the CVE record (20 products)
Rockwell Automation 1756-EN2T Series A, B, C
StatusVersions
Affected<=5.008 & 5.028

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2T Series D
StatusVersions
Affected<=11.003

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2TK Series A, B, C
StatusVersions
Affected<=5.008 & 5.028

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2TXT Series A, B, C
StatusVersions
Affected<=5.008 & 5.028

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2TXT Series D
StatusVersions
Affected<=11.003

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2TP Series A
StatusVersions
Affected<=11.003

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2TPK Series A
StatusVersions
Affected<=11.003

Versions not listed are: unaffected.

Rockwell Auotmation 1756-EN2TPXT Series A
StatusVersions
Affected<=11.003

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2TR Series A, B
StatusVersions
Affected<=5.008 & 5.028

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2TR Series C
StatusVersions
Affected<=11.003

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2TRK Series A, B
StatusVersions
Affected<=5.008 & 5.028

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2TRK Series C
StatusVersions
Affected<=11.003

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2TRXT Series A, B
StatusVersions
Affected<=5.008 & 5.028

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2TRXT Series C
StatusVersions
Affected<=11.003

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2F Series A, B
StatusVersions
Affected<=5.008 & 5.028

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2F Series C
StatusVersions
Affected<=11.003

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2FK Series A, B
StatusVersions
Affected<=5.008 & 5.028

Versions not listed are: unaffected.

Rockwell Automation 1756-EN2FK Series C
StatusVersions
Affected<=11.003

Versions not listed are: unaffected.

Rockwell Automation 1756-EN3TR Series A
StatusVersions
Affected<=5.008 & 5.028

Versions not listed are: unaffected.

Rockwell Automation 1756-EN3TR Series B
StatusVersions
Affected<=11.003

Versions not listed are: unaffected.

Source: CVE List, as of . About the data.

Weakness

CWE-787, 1 CAPEC

Attack patterns (CAPEC)

CWE and CAPEC are maintained by MITRE; the entries are those named in the CVE record.

Timeline

DateEvent
CVE record published
CVE record last updated

References

1

Known exploited Rockwell Automation vulnerabilities

  • CVE-2021-22681: Rockwell Multiple Products Insufficient Protected Credentials Vulnerability (added )